Инструкция кондиционер настенный сплит-система Samsung AR18BXHQASINUA/AR18BXHQASIXUA

Instructions for Connecting Piping to Indoor Unit (стр. 31 из 208)

Бренд: Samsung

Страница 31 документа Кондиционер настенный сплит-система Samsung AR18BXHQASINUA/AR18BXHQASIXUA. Раздел: Кондиционеры (сплит-системы). Бренд: Samsung.

Текст страницы

PIPING EXTENSION BEYOND FLARE FORM

Max.

Outer Diameter of
Pipe (mm)
A (mm)

Min.
Max.

Step 2: Remove burrs
Burrs can affect the air-tight seal of refrigerant
piping connection. They must be completely
removed.

Ø 6.35 (Ø 0.25”)
0.7 (0.0275”)
1.3 (0.05”)

Ø 9.52 (Ø 0.375”)
1.0 (0.04”)
1.6 (0.063”)

Ø12.7 ( Ø 0.5”)
1.0 (0.04”)
1.8 (0.07”)

1. Hold the pipe at a downward angle to prevent
burrs from falling into the pipe.
2. Using a reamer or deburring tool, remove all
burrs from the cut section of the pipe.

Ø 16 ( Ø 0.63”)

2.0 (0.078”)
2.2 (0.086”)

2.0 (0.078”)
2.4 (0.094”)

Ø 19 ( Ø 0.75”)

Pipe
Reamer

Flare form

A

Point down

Pipe

6. Place flaring tool onto the form.
7. Turn the handle of the flaring tool clockwise
until the pipe is fully flared.
8. Remove the flaring tool and flare form, then
inspect the end of the pipe for cracks and
even flaring.

Step 4: Connect pipes

Step 3: Flare pipe ends
Proper flaring is essential to achieve an airtight
seal.
1. After removing burrs from cut pipe, seal
the ends with PVC tape to prevent foreign
materials from entering the pipe.
2. Sheath the pipe with insulating material.
3. Place flare nuts on both ends of pipe. Make
sure they are facing in the right direction,
because you can’t put them on or change
their direction after flaring.

When connecting refrigerant pipes, be careful
not to use excessive torque or to deform the
piping in any way. You should first connect the
low-pressure pipe, then the high-pressure pipe.

Flare nut

Copper pipe

MINIMUM BEND RADIUS
When bending connective refrigerant piping,
the minimum bending radius is 10cm.

4. Remove PVC tape from ends of pipe when
ready to perform flaring work.

≥10cm (4in)
Radius

5. Clamp flare form on the end of the pipe.
The end of the pipe must extend beyond the
edge of the flare form in accordance with the
dimensions shown in the table below.

Instructions for Connecting Piping to Indoor Unit

1. Align the center of the two pipes that you will
connect.

Indoor unit tubing
Flare nut
Pipe

Refrigerant piping
Connection