Self diagnosis function

■ We are constantly trying to do better service to our customers by installing such judges that show abnormality of each function as follows

RUN light

Description of trouble
Cause

1-time flash

Indoor heat exchanger sensor 1
error

• Broken heat exchanger sensor 1 wire, poor connector
connection

Room temperature sensor error

2-time flash

• Broken room temperature sensor wire, poor connector
connection

3-time flash

Indoor heat exchanger sensor 3
error

• Broken heat exchanger sensor 3 wire, poor connector
connection

4-time flash

Trouble of Wireless LAN interface

TIMER light ON

• Defective Wireless LAN interface boards, poor connector
connection

5-time flash

Circuit error

• Circuit failure or poor connector connection

Indoor fan motor error

• Defective fan motor, poor connector connection

6-time flash

7-time flash

  • Refrigerant is insufficient, leaking
  • Closed service valve

Refrigerant is insufficient
Closed service valve

TIMER light

• Broken outdoor sensor wire, poor connector connection

Outdoor temperature sensor error

1-time flash

2-time flash

Outdoor heat exchanger sensor
error

• Broken heat exchanger sensor wire, poor connector
connection

RUN light keeps flashing

Discharge pipe sensor error

• Broken discharge pipe sensor wire, poor connector connection

4-time flash

• Broken suction pipe sensor wire, poor connector connection

5-time flash

Suction pipe sensor error

Current cut

1-time flash

• Compressor locking, open phase on compressor output,
short circuit on power transistor, closed service valve

Trouble of outdoor unit

2-time flash

  • Broken compressor wire
  • Compressor blockage

Over current

• Overload operation, overcharge of refrigerant

3-time flash

• Broken power transistor

Power transistor error

4-time flash

RUN light ON

Over heat of compressor

5-time flash

• Gas shortage, defective discharge pipe sensor,
closed service valve

Error of signal transmission

6-time flash

• Defective power source, broken signal wire, defective
indoor/outdoor unit boards

7-time flash

Outdoor fan motor error

• Defective fan motor, poor connector connection

Keep flashing

Cooling high pressure protection

• Overcharge of refrigerant, short circuit of outdoor unit

2-time flash

RUN light 2-time flash

Rotor lock
• Defective compressor
• Open phase on compressor
• Defective outdoor unit boards

1-time flash

Closed service valve
• Closed service valve

RUN light 7-time flash

EN-34